2.2.63. Meter Table Configuration Command Class, version 1

The Meter Table Configuration Command Class defines the Commands necessary to configure the fundamental properties of the meter.

The Meter Table configuration commands are separated from the Meter Table monitoring commands in the Meter Table Monitor Command Class, allowing the classes to be optionally supported at different Z-Wave security levels. (E.g. Meter table monitoring commands could be supported in any device, while enabling a strict and certificate based security solution for the Meter Table Configuration Command class). Refer to Section 4 for more details about Z-Wave security.

2.2.63.1. Meter Table Point Adm Number Set Command

This command is used to set the Meter Point Administration Number in the metering device. The Meter Point Administration Number is used to identify the customer.

Table 2.373 Meter Table Point Adm Number Set Command

7

6

5

4

3

2

1

0

Command Class = COMMAND_CLASS_METER_TBL_CONFIG (0x3C)

Command = METER_TBL_TABLE_POINT_ADM_NO_SET (0x01)

Reserved

Number of Meter Point Adm Number Characters

Meter Point Adm Number Character 1

Meter Point Adm Number Character N

Reserved

This field MUST be set to 0 by a sending node and MUST be ignored by a receiving node.

Number of Meter Point Adm Number Characters (5 bits)

Number of characters in the meter point administration number(1…32).

Meter Point Adm Number Character (N bytes)

The Meter Point Adm Number character fields hold the string identifying the customer. The character presentation uses standard ASCII codes (values 128-255 are ignored).